The 14 steps of the termination procedure.

STEP 1: Cut cable end square.  Slide gland onto cable.

terminating_proceedure_1

STEP 2: Apply pyro stripper and turn clockwise to remove sheath.

terminating_proceedure_2

STEP 3: Use pliers to stop stripper at required point and clean powder from exposed conductors.

terminating_proceedure_3

STEP 4: Alternatively use joistripper tool for popular 500v cables.

terminating_proceedure_4

STEP 5: Using pliers/pyro potter, screw seal pot onto cable as shown. Remove loose powder and metallic swarf.

terminating_proceedure_5

STEP 6: When using disc type closure, position headed conductor sleeves correctly as shown.

terminating_proceedure_6

STEP 7: Completely fill pot with compound from one side only.

terminating_proceedure_7

STEP 8: Apply pressure to enter stub cap or disc into pot recess.

terminating_proceedure_8

STEP 9: Use pyro crimp tool, compress compound and secure pot closure.

terminating_proceedure_9

STEP 10: Alternatively use pyro-x-crimp plate type tool.

terminating_proceedure_10

STEP 11: Fit conductor sleeving if using stub cap closure.

terminating_proceedure_11

STEP 12: Before fitting gland and seal cut shroud to ensure tight fit over outer covering.

terminating_proceedure_12

STEP 13: Then remove required length of covering.

 

terminating_proceedure_13

STEP 14: In corrosive environments use PVC tape to protect exposed copper sheath and gland after fitting cable into apparatus.

terminating_proceedure_14

DONE!